Valve con­trol – HE 5721

for up to 24 cleaning valves

Differential pressure or time-controlled cleaning

Available with and without front panel operation

Settings via potentiometer

Suitable for use in ATEX Zone 22

 

 

 

Produkt anfragen

 

 

The HE 5721 valve con­trol unit is used to pulse sole­noid valves in indus­trial dust extrac­tion tech­nol­ogy.
The con­trol unit imple­ments numer­ous con­trol and mon­i­tor­ing func­tions and can option­ally be equipped with dif­fer­en­tial pres­sure mea­sure­ment and con­trol. Clean­ing is time-con­trolled or dif­fer­en­tial pres­sure-depen­dent (with optional dp con­troller) with switch­ing thresh­olds or pause time con­trol. The 12 valves are mon­i­tored for over­cur­rent (short cir­cuit) and inter­rup­tion. With an exten­sion unit, up to 24 valves can be con­trolled and mechan­i­cal valve func­tion mon­i­tor­ing with a pres­sure switch is avail­able as an option.

 

The HE 5721 valve con­trol unit is suit­able for use in explo­sion zone 22. For safe con­nec­tion, we rec­om­mend the ATEX con­nec­tion set # 57210088 incl. Mul­ti­ple den­sity inserts.

Set­ting options for the HE 5721 valve con­trol unit

The time set­tings of the poten­tiome­ters have a log­a­rith­mic divi­sion

  • Pulse time: 0.02 … 1.2 s
  • Pause time: 1 … 270 s
  • Num­ber of valves: 1 … 12 valves (can be extended to 1 … 24 valves)
  • Post-clean­ing cycles: 0 … 12
  • Post-clean­ing start: 0 … 100% of the mea­sur­ing range end value of the dif­fer­en­tial pres­sure mea­sure­ment

 

Fur­ther set­ting options for the HE 5721 valve con­trol unit

  • “Clean­ing stop” switch­ing thresh­old
  • “Clean­ing start” switch­ing thresh­old
  • Alarm thresh­old
  • dp zero point

 

Com­pre­hen­sive tech­ni­cal data can be found in the respec­tive oper­at­ing instruc­tions.

Technical data

HE 5721 ohne Front­platte
EingängeStart- oder dp-Ein­gang 0(4)...20 mA
• Freigabe (Kon­takt geschlossen) / Stopp (Kon­takt offen)
• Nachreini­gung (Tastsig­nal)
• Störquit­tierung (Tastsig­nal)
• Druckschal­ter zur mech­a­nis­chen Ven­til­funk­tion­süberwachung (Option)
Ven­ti­laus­gänge12, mit Erweiterung max. 24 (Option)
Ven­tilspan­nung24 V DC ± 10 %
Ven­til­strom1 A (bei Pul­szeit ≤ 1 s und Pausen­zeit ≥ Pul­szeit), sonst 0,5 A
Nennleis­tung Ven­ti­laus­gangmax. 24 Watt
Anzeigen• 3-stel­lige Dig­i­tal-Anzeige (7-Seg­ment)
• 12 (24) LEDs für Ven­ti­lans­teuerung
• 1 LED 'Betrieb' (grün)
• 1 LED 'Störung' (rot)
• 1 LED 'Reini­gung' (gelb)
Betrieb­s­funk­tio­nen• Teil-/Ge­samtzyk­lus
• dif­feren­z­druck­ab­hängige Regelung
• Ven­til­stromüberwachung (Kurzschluss/Unterbrechung)
• mech. Ven­til­funk­tion­süberwachung (Option)
Test­funk­tion1 Taster für Ven­til­funk­tion­stest
Relaisaus­gängeKon­tak­t­be­las­tung 250 VAC / 5 A:
• 1 Wech­sler für Betriebs-/Stör- mel­dung (fail-safe-Schal­tung),
• 1 Schließer für Reini­gungsmeldung
Ein­stellmöglichkeiten• Ven­ti­lan­zahl 1...12 (24)
• Pul­szeit 0,02...1,2 s
• Pausen­zeit 1...270 s
• Nachreini­gung 0...12 Zyklen
• Nachreini­gung Start 0...100% Messb.
• Schaltschwelle 'Reini­gung Stop'
• Schaltschwelle 'Reini­gung Start'
• Alarm­schwelle
• dp-Nullpunkt
dp-Regler
Mess­bere­ichezwis­chen 0...25 und 0...500 mbar
dp-Sen­sor:• max. sta­tis­cher Druck: 1000 mbar
• Lin­ear­ität: ±1%
• Hys­terese: ±0,1 %
• Tem­per­atur-Hys­terese: ± 0,5 %
• Tem­per­atur­drift / Nullpunkt: ± 0,025 %/K
• Tem­per­atur­drift / Endw­ert: ± 0,01 %/K
Ana­log-Aus­gang:0(4)...20 mA
Relaisaus­gänge1 Schal­taus­gang (Wech­sler) für Δp-Alarm
Schaltleis­tung 250 V AC, 5A
Druck­an­schlüsseSchlauchver­schraubung DN 4
All­ge­meine Tech­nis­che Daten
Net­zver­sorgung100 – 240 VAC ± 10 %, 50-60 Hz
(Option: 24 VDC)
Net­zsicherung0,315 A träge (TR5) (3,15A)
Leis­tungsauf­nahme30 VA (42 W)
Elektr. AnschlussSchraubklemm­leis­ten 2,5 mm²
Ven­ti­lan­schlüsse 1,0 mm²
Arbeit­stem­per­atur20 °C...50 °C
(In Ex-Zone 22: -20 °C…+40 °C)
Stör­fes­tigkeitDIN EN 50081 Teil 1
DIN EN 50082 Teil 2
SchutzartIP65
Abmes­sung180 × 180 × 75 mm (B × H × T)
Aus­führungstaub­dichtes Makro­longe­häuse (IP65) mit Gewinde M20 x 1,5 und 2x M32 x 1,5 für metrische Ver­schraubun­gen. Öff­nun­gen sind, falls erforder­lich, mit Ver­schlusss­chrauben staub­dicht (IP65) zu ver­schließen.
1 Ver­schlusss­chraube M32 enthal­ten
Gerätekennze­ich­nung II3D Ex Tc IIIC T135°C Dc IP65CE EX Logo

Errors and omis­sions excepted

Downloads

Oper­at­ing instruc­tions HE 5721 with front panel – Eng­lish

Oper­at­ing instruc­tions HE 5721 with front panel – Ger­man

Oper­at­ing instruc­tions HE 5721 with­out front panel – Eng­lish

Oper­at­ing instruc­tions HE 5721 with­out front panel – Ger­man

    Hier können Sie uns eine Datei senden:

     

    captcha

    ACHTUNG: Zum Absenden des Formulars muss der rechtliche Hinweis mit einem Häkchen bestätigt werden.

    preloader